1MRS756711 D
2.3.1.17
Table 20:
LD0.DPHHPDOC1 Three-phase directional overcurrent protection - high stage (1)
IEC 61850 name
LD0.DPHHPTOC1
.Op.general
.Str.general
2.3.1.18
Table 21:
LD0.EFHPTOC1 Non-directional earth-fault and sensitive earth-fault protection - high stage 1
IEC 61850 name
LD0.EFHPTOC1
.Op.general
.Str.general
2.3.1.19
Table 22:
LD0.EFIPTOC1 Non-directional earth-fault and sensitive earth-fault protection - instantaneous stage 1
IEC 61850 name
LD0.EFIPTOC1
.Op.general
.Str.general
2.3.1.20
Table 23:
LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault protection - low stage 1
IEC 61850 name
LD0.EFLPTOC1
.Op.general
.Str.general
REF615
Point List Manual
LD0.DPHHPDOC1 Three-phase directional overcurrent protection -
high stage (1)
SA name
OPERATE
START
LD0.EFHPTOC1 Non-directional earth-fault and sensitive earth-fault
protection - high stage 1
SA name
OPERATE
START
LD0.EFIPTOC1 Non-directional earth-fault and sensitive earth-fault
protection - instantaneous stage 1
SA name
OPERATE
START
LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault
protection - low stage 1
SA name
OPERATE
START
Description
High stage (1)
-Operate
-Start
Description
High stage (1)
-Operate
-Start
Description
Instant. stage (1)
-Operate
-Start
Description
Low stage (1)
-Operate
-Start
Section 2
DNP3 data mappings
Values
1=Operate
1=Start
Values
1=Operate
1=Start
Values
1=Operate
1=Start
Values
1=Operate
1=Start
21