Section 2
DNP3 data mappings
2.3.2.13
Table 94:
LD0.SRGAPC2 Multipurpose binary outputs - flip-flop resets (2)
IEC 61850 name
.Rs1.ctlVal
.Rs2.ctlVal
.Rs3.ctlVal
.Rs4.ctlVal
.Rs5.ctlVal
.Rs6.ctlVal
.Rs7.ctlVal
.Rs8.ctlVal
2.3.2.14
Table 95:
LD0.SSCBR1 Reset signals of CB condition monitoring
IEC 61850 name
LD0.SSCBR1
.RsAccAPwr.Oper.ctlVal
.RsCBWear.Oper.ctlVal
.RsSprChaTm.Oper.ctlVal
.RsTrvTm.Oper.ctlVal
2.3.3
40
LD0.SRGAPC2 Multipurpose binary outputs - flip-flop resets (2)
SA name
-
-
-
-
-
-
-
-
LD0.SSCBR1 Reset signals of CB condition monitoring
SA name
RST_IPOW
RST_CB_WEAR
RST_SPR_T
RST_TRV_T
Analog inputs
Table 96:
Explanations of the analog input table columns
Column name
Description
IEC 61850
Original IED data object identification. Described in the IEC 61850 format as
name
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible for example in ACT.
Description
Short description of the signal. See the application function block documentation
for more details.
Values
The value range of the original IEC 61850 data. Scaling is needed to convert
floating point data into DNP3 integer values.
S
Scaling type selected as default. Default "R" means ratio scaling. See the DNP
communication protocol manual for details.
Arg 1, 2, 3, 4
Scaling argument values as default. When ratio scaling is selected, the four
values correspond to min value in, max value in, min value out, and max value
out. See the DNP communication protocol manual for details.
Description
Reset flip-flop 1
Reset flip-flop 2
Reset flip-flop 3
Reset flip-flop 4
Reset flip-flop 5
Reset flip-flop 6
Reset flip-flop 7
Reset flip-flop 8
Description
Reset accum. energy
Reset CB life and op. counter
Reset spring charge alarm
Reset travel time alarm
1MRS756711 D
Type
On
On
On
On
On
On
On
On
Type
On
On
On
On
REF615
Point List Manual