Ctrl.essxswi2 Earth Switch 2, 4-Pole (2 Bit) Position Values; Ctrl.esxswi1 Controllable Earth Switch 1, 4-Pole (2 Bit) Position Values; Ld0.Dnpggio1 Active Parameter Setting Group; Ld0.Fmmxu1 Frequency Measurement - ABB Relion 615 Series Point List Manual

Feeder protection and control
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

1MRS756711 D
2.3.3.11
Table 107:

CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position values

IEC 61850 name
SA name
CTRL.ESSXSWI2
.Pos.stVal
2.3.3.12
Table 108:

CTRL.ESXSWI1 Controllable earth switch 1, 4-pole (2 bit) position values

IEC 61850 name
SA name
CTRL.ESXSWI1
.Pos.stVal
2.3.3.13
Table 109:

LD0.DNPGGIO1 Active parameter setting group

IEC 61850 name
SA name
LD0.DNPGGIO1
.ActSG.stVal
2.3.3.14
Table 110:

LD0.FMMXU1 Frequency measurement

IEC 61850 name
SA name
LD0.FMMXU1
.Hz.mag
2.3.3.15
Table 111:

LD0.HAEFMHAI1 Current harmonics

IEC 61850 name
SA name
LD0.HAEFMHAI
.HRmsA.res.cVal.mag
REF615
Point List Manual
CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position values
Description
Intermediate=0; Off=1; On=2;
POSITION
Bad=3
CTRL.ESXSWI1 Controllable earth switch 1, 4-pole (2 bit) position
values
Description
Intermediate=0; Off=1; On=2;
POSITION
Bad=3
LD0.DNPGGIO1 Active parameter setting group
Description
-
Active setting group
LD0.FMMXU1 Frequency measurement
Description
-
Frequency value
LD0.HAEFMHAI1 Current harmonics
Description
-
Current harmonics
DNP3 data mappings
Values
S
Arg 1,2,3,4
0...3
R
0,3,0,3
Values
S
Arg 1,2,3,4
0...3
R
0,3,0,3
Values
S
Arg 1,2,3,4
1...6
R
1,6,1,6
Values
S
Arg 1,2,3,4
35...75 [Hz]
R
35,75,3500,7500
Values
S
Arg 1,2,3,4
0...250 [A]
R
0,250,0,250