Section 2
DNP3 data mappings
2.3.2
2.3.2.1
Table 82:
CTRL.CBCSWI1 Circuit breaker control
IEC 61850 name
CTRL.CBCSWI1
.Pos.Oper.ctlVal
2.3.2.2
Table 83:
CTRL.DCCSWI1 Controllable disconnector (1) control
IEC 61850 name
CTRL.DCCSWI1
.Pos.Oper.ctlVal
2.3.2.3
Table 84:
CTRL.DCCSWI2 Controllable disconnector (2) control
IEC 61850 name
CTRL.DCCSWI2
.Pos.Oper.ctlVal
2.3.2.4
Table 85:
CTRL.ESCSWI2 Controllable earth switch (1) control
IEC 61850 name
CTRL.ESCSWI1
.Pos.Oper.ctlVal
36
Binary outputs
Table 81:
Explanations of the binary output table columns
Column name
Description
IEC 61850
Original IED data object identification. Described in the IEC 61850 format as
name
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible for example in ACT.
Description
Short description of the signal. See the application function block documentation
for more details.
Type
Output type. Some outputs can only be controlled with value "On". Writing "Off" to
these points does not affect the function of the output. See DNP3 control relay
output block parameters.
CTRL.CBCSWI1 Circuit breaker control
SA name
-
CTRL.DCCSWI1 Controllable disconnector (1) control
SA name
-
CTRL.DCCSWI2 Controllable disconnector (2) control
SA name
-
CTRL.ESCSWI2 Controllable earth switch (1) control
SA name
-
Description
Circuit breaker control
Description
Disconnector control
Description
Disconnector control
Description
Earth switch control
1MRS756711 D
Type
On/Off
Type
On/Off
Type
On/Off
Type
On/Off
REF615
Point List Manual