Ld0.Arcsarc1 Fault Arc Protection Stage 1; Ld0.Arcsarc2 Fault Arc Protection Stage 2; Ld0.Arcsarc3 Fault Arc Protection Stage 3; Ctrl.cxxxxx1 Circuit Breaker (1) Cb Object And Failure Protection - ABB Relion 615 Series Point List Manual

Feeder protection and control
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

Section 2
DNP3 data mappings
2.3.1.1
Table 4:

LD0.ARCSARC1 Fault arc protection stage 1

IEC 61850 name
LD0.ARCSARC11
.FADet.stVal
LD0.ARCPTRC11
.Op.general
2.3.1.2
Table 5:

LD0.ARCSARC2 Fault arc protection stage 2

IEC 61850 name
LD0.ARCSARC21
.FADet.stVal
LD0.ARCPTRC21
.Op.general
2.3.1.3
Table 6:

LD0.ARCSARC3 Fault arc protection stage 3

IEC 61850 name
LD0.ARCSARC31
.FADet.stVal
LD0.ARCPTRC31
.Op.general
2.3.1.4
Table 7:

CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection

IEC 61850 name
CTRL.CBCILO1
.EnaCls.stVal
.EnaOpn.stVal
.ItlByPss.stVal
CTRL.CBCSWI1
.Pos.stSeld
CTRL.CBXCBR1
.BlkCls.stVal
.BlkOpn.stVal
Table continues on next page
16
LD0.ARCSARC1 Fault arc protection stage 1
SA name
ARC_FLT_DET
OPERATE
LD0.ARCSARC2 Fault arc protection stage 2
SA name
ARC_FLT_DET
OPERATE
LD0.ARCSARC3 Fault arc protection stage 3
SA name
ARC_FLT_DET
OPERATE
CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection
SA name
ENA_CLOSE
ENA_OPEN
ITL_BYPASS
SELECTED
BLK_CLOSE
BLK_OPEN
Description
Arc detected
Operate
Description
Arc detected
Operate
Description
Arc detected
Operate
Description
Close enabled
Open enabled
Interlocking bypass
CB selected
Close blocked
Open blocked
1MRS756711 D
Values
1=Detected
1=Operate
Values
1=Detected
1=Operate
Values
1=Detected
1=Operate
Values
1=Enabled
1=Enabled
1=Bypassed
1=Selected
1=Blocked
1=Blocked
REF615
Point List Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ref615

Table of Contents