Troubleshooting Guide

POSSIBLE ISSUES
No power or low power
Reduced Holding Force

LED Error Codes

NOTE:
The position 1 switch of DIP switch SW3 must be set to the ON position (LED
ENABLED) for error codes to be visible.
CODE
SECURE selected color, on
continuously
NON-SECURE selected
color, on continuously
RED/GREEN
continuous
flash
3 Fast Flashes of SECURE
color every 5 seconds
Single Flash Amber every 5
seconds
Double Flash Amber every 5
seconds
Off

Problems with Installation?

Call Securitron: 1.800.MAGLOCK
For warranty information: www.securitron.com/warranty
Email: techsupport@securitron.com
© 2015, Hanchett Entry Systems, Inc., an ASSA ABLOY Group company.
TROUBLESHOOTING TIPS
CONFIRM voltage and current at Magnalock to spec
CHECK that the DC Power Source is Full Wave Rectified
(Half wave Rectified or AC power is unacceptable).
CHECK strike plate position and orientation.
CLEAN surfaces and CHECK for obstructions.
STATE
Normal Operation with Door
Closed
Normal Operation with Door
Open
Processor Error
Magnet Voltage has dropped
below 85%
Bond Error – Left Side
Bond Error – Right Side
LED disabled
Page 20
SOLUTION
System working normally, SECURE selected color
can be selected with position 2 switch of SW3.
See page 4.
System working normally.
CHECK all connections, if error persists replace
unit.
CHECK voltage and current at Magnalock
connections. CHECK DC Power Source is Full
Wave Rectified.
CHECK strike plate position and orientation.
CLEAN surfaces and check for obstructions.
CHECK strike plate position and orientation.
CLEAN surfaces and check for obstructions.
CHECK voltage and current at Magnalock
connections. CHECK that LED is enabled with
position 1 switch of SW3 is in the OFF position.