3 11
Selective Hold Open Cam Adjustment
Setting Hold Open Angle
• Make all required electrical connections
and turn power switch to on for non-
detectored units (detectored units
cannot be turned off at the closer). (See
previous step)
• Open door to desired hold open angle.
• Loosen cam screw and rotate cam until
switch closes and door holds open.
• Rotate cam until it touches the switch.
• Tighten cam screw but do not over
torque as this will cause damage to
cam.
• Force door out of hold open by closing
the door, then test hold open by
opening to hold open angle again.
c
SHO switch in
open position.
Closer not in
hold open.
3 12
Attach Cover
Attach cover using screws provided.
Copyright © 2010, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
a
d
Right hand pull-side shown.
Switch shown in hold open position (closed).
Un-used pin
6
b
5/32" hex
wrench
Backplate
SHO switch in
closed position.
Closer in hold
open.
RIXSON
ASSA ABLOY
5/32" hex
wrench
e
80-9372-0100-015 (02-14)
®