Closer Adjustments

Closing Speed Controls
• Valve "S" Controls Sweep Range from
full open to 5°.
• Valve "L" Controls Latch Range from 5°
to closed.
Opening Cycle
• Valve "B" controls the strength of
cushioning in Backcheck Range.
NEVER close this valve completely – it
is not to provide a positive stop.
• Valve "P" adjusts the angle that back-
check is felt in the open cycle.
"B"
Backcheck
Stronger
+
1/8"
Hex
Key
-
Weaker
11
3
Electrical Connections
See Page 13 for Non-Detectored Units
See Page 14 for Detectored Units
See Page 15 for RF Units
Copyright © 2010, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
75°
!
Never Close
backcheck valve
completely
"S"
Sweep
1/8"
Hex
Key
"P"
Backcheck
Position
1/8"
Hex
Key
90°
75°
10
RIXSON
ASSA ABLOY
"L"
Latch
1/8"
Hex
Key
!
Do not remove valves
from closer. Hydraulic
oil will escape.