10.1.2
VFD Faceplate Parameter Access
Call up the VFD Parameter list with the VFD keypad.
Press and hold the Navigate key > 2 seconds.
Figure 46: Navigate Key
You should see the parameters on the VFD faceplate display.
You can press the up and down Arrow Buttons to look at the various parameters.
Press the Navigate key once quickly to see the value of the parameter selected.
10.1.3
VFD Suite Real-Time Edit and Drive Monitor Tool
1. Click the Real-Time Edit Mode button to enable Real-Time mode.
2. Scroll down to the Parameter P0-65 Drive Life Time row and select the box in the Refresh
Column.You should see dynamic data updating in the Value Column.
3. Choose File-Save Parameter Set as your backup copy of the Real-Time parameters.
To select the Drive Monitor Tool, you must briefly leave the Real-Time Edit mode.
4. Click Disable Real-Time Edit.
5. Click Tools-Drive Monitor Tool.
6. Click the Enable Real-Time Monitor button.
7. In the Local column select the box for the VFD on your list.
You should see Live data on the Monitor Screen.
Figure 47: Local Column
8. Start the Drive by pressing the green Start The Motor button (motor will RUN if
permissions are true).