Bosch Rexroth AG
Mounting, demounting and electric installation
10 Mounting, demounting and electric installation
10.1 Installation notes
10.1.1 Cables routing
Lay all connecting cables in loops and use strain reliefs for all cables
●
Keep the maximum distance possible from interference sources
●
Do not lay the CDI cables in parallel to motor cables or to other noise
●
sources, as the CDI connection can be disturbed
10.1.2 Housing distances for maintenance tasks
Provide a space on all sides of the device for sufficient cooling and cable routing
Comply with the following housing distances to execute maintenance tasks
directly at the device in the control cabinet:
To maintain the fan and exchange the battery, go up by 120 mm (refer to the
●
following figure).
For changing the hard disk 150 mm to the front (refer to the following figure).
●
In the installed state, the internal connections of USB, mSATA and mPCIe
●
have to be accessible. Ensure sufficient distance on the right. For the position
of the connections, refer to
mSATA modules and mPCIe modules" on page
Fig. 10-1: Housing distances for maintenance tasks
20/87
chapter 10.1.3 "Internal connections for USB,
120 mm
150 mm
IndraControl VPB 40.4
21.
DOK-MLC***-INDRACTRLV4-IT02-EN-P