Verifying The Settings - ABB Relion 670 Series Commissioning Manual

Transformer protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
11.5.18.2

Verifying the settings

Verifying settings by secondary injection
1.
Connect the test set for three-phase current injection and three-phase voltage injection to the
appropriate IED terminals.
2.
Go to Main menu /Settings /IED Settings /Current protection /VoltageRestOverCurr ( 51V,2(I>/
V<))/VRPVOC (51V,2(I>/V<)):1 /General and make sure that the function is enabled, that is,
Operation is set to Enabled.
3.
The test of the function may be performed by injecting restrain voltage and increasing the injected
current(s). Note the value at which the PICKUP and STOC signals are set.
The set trip value in secondary amperes is calculated according to the following equations:
First part of the characteristic (Restrain voltage ≤ 25% of VBase):
Picup Curr
ANSI13000291 V1 EN-US
Second part of the characteristic (25% of VBase ≤ Restrain voltage ≤ VHighLimit/100*VBase), valid
when setting parameter VDepMode = Slope:
Pickup Curr
 
ANSIEQUATION2433 V2 EN-US
Third part of the characteristic (VHighLimit/100*VBase ≤ Restrain voltage):
Picup Curr
ANSIEQUATION2434 V1 EN-US
Example (rated secondary current = 5A):
CT ratio
VT ratio
Pickup_Curr
VDepFact
VHighLimit
IBase
VBase
A test for each section of the characteristic of the function VRPVOC may be performed; that may
be achieved by applying the following voltages:
First section of the characteristic:
198
In the following equations, restrain voltage is the magnitude of the minimum phase-
to-phase voltage in secondary volts.
_
sec
CT
VDepFact
IBase
×
×
×
100
CTprim
_
CT
sec
VDepFact
×
×
 ×
IBase
1
100
CTprim
100
(
)
V V HighLimit
25
VT
sec
×
×
VBase
100
VTprim
_
CT
sec
IBase
×
×
100
CTprim
© 2017 - 2021 Hitachi Power Grids. All rights reserved
100
25
VT
sec
×
×
×
Re
strainVoltage
VBase
10
0 0
VTprim
10 000/5A
10 kV/100 V
100%
25%
100%
10 000 A
10 kV
1MRK 504 165-UUS Rev. J
GUID-3A2B7FF5-330E-4A0D-AB74-EBAE6258C176 v1
GUID-39632D30-A8D8-417D-985C-8F886106783E v4
Pickup Curr
_
CT
sec
VDepFact
+
×
×
×
IB
a a se
100
CTprim
100
 
Transformer protection RET670
Commissioning manual
(Equation 95)
(Equation 96)
(Equation 97)