ABB Relion 670 Series Commissioning Manual page 113

Transformer protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 504 165-UUS Rev. J
To verify the settings for the operating points according to the following fault types should be tested:
One phase-to-phase fault
One phase-to-ground fault
The shape of the operating characteristic depends on the values of the setting parameters.
X1set
ANSI05000368 V2 EN-US
Figure 25:
Table 20:
Test point
1
2
3
4
Table continues on next page
Transformer protection RET670
Commissioning manual
The figures illustrating the characteristic for the distance protection function can be used
for settings with and without load encroachment. The solid lines designate the diagram
applicable when the load current compensation is active. The solid line and all test points
except 13 are valid for this case.
When the load current compensation is inactive, the dotted lines and test point 13 are
valid. Test points 5, 6, and 7 are not valid for this measurement.
X
2
1
11
10
12
9
8
25% of RFPPZx/2
50% of RFPPZx/2
RFPP/2
Distance protection characteristic with test points for phase-to-phase measurements
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Reach
Set value
X
X1
set
R
0
X
X1
set
R
R1
set
X
0.8 x X1
set
R
0.8 x R1
+ RFPP/2
set
X
0.5 x X1
set
R
0.5 x R1
+ RFPP/2
set
© 2017 - 2021 Hitachi Power Grids. All rights reserved
80%
3
50%
4
5
ArgLd
6
R
(Ω/phase)
7
13
ArgDir
ANSI05000368-2-en.vsdx
Comments
Section 11
Testing functionality by secondary injection
107