ABB Relion 670 Series Commissioning Manual page 124

Transformer protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
Test point
10
11
12
13
Table 27:
Test point
1
2
3
4
5
6
7
8
9
10
11
Table continues on next page
118
Reach
Set value
X
0.5 x X1
set
R
–0.23 x X1
set
X
0.8 x X1
set
R
–0.37 x X1
set
X
0.5 x X1
set
R
0.5 x R1
set
X
0
R
0.5 x RFPP
Test points for phase-to-earth L3-G (Ohm/Loop)
Reach
Value
X
(2 x X1
+X0
set
R
0
X
(2 x X1
+ X0
set
R
2 x R1
+ R0
set
X
0.8 x (2 x X1
set
R
0.8 x (2 x R1
+RFPG
set
X
0.5 x (2 x X1
set
R
0.5 x (2 x R1
RFPG
set
X
0.85 x RFPG
R
0.85 x RFPG
X
RLdFwdset x tan(LdAngleSet)
R
RLdFwd
set
X
0
R
RLdFwd
set
X
–02143 x RLdFwd
R
0.8 x RLdFwd
X
–0.8 x RLdFwd
R
0.8 x RLdFwd
X
0.17 x (2 x X1
R
-0.36 x (2 x X1
X
0.27 x (2 x X1
R
–0.57 x (2 x X1
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Comments
Exact –0.5 x R1
Exact –0.5 x R1
Only used when OperationLdCmp setting is 0 (Disabled)
Comments
)/3
set
)/3
set
)/3
set
+ X0
)/3
set
+ R0
)/3
set
set
+ R0
)/3
set
+R0
)/3 +
set
set
x tan(LdAngleset)
LdAngle = angle for the maximal load transfer.
set
Exact: 0.8 x RFPG x tan (ArgDir)
set
set
x tan(ArgDir)
set
set
+ X0
)
Exact: 0.5 x (2 x X1
set
set
+ X0
)
Exact: 0.5 x (2X1
set
set
+X0
)
Exact: 0.8 x (2 x X1
set
set
+ X0
)
Exact: 0.8 x (2X1set + X0set)/(3 x tan(AngNegDir 90))
set
set
1MRK 504 165-UUS Rev. J
x tan(ArgNegRes-90)
set
x tan(ArgNegRes-90)
set
X0
)/3
set
set
+ X0
)/(3 x tan(AgNegDir90)
set
set
+ X0
)/3
set
set
Transformer protection RET670
Commissioning manual