Figure 44:
11.4.13

Automatic switch onto fault logic ZCVPSOF

Prepare the IED for verification of settings outlined in Section
The automatic switch onto fault logic function ZCVPSOF is checked using secondary injection tests.
ZCVPSOF is activated either by the external input BC or by the internal DLD. FUFSPVC is done with a
pre-fault condition where the phase voltages and currents are at zero. A three-phase fault with zero
impedance and a three-phase fault with an impedance corresponding to the whole line is applied. This
fault shall cause an instantaneous trip and result in a TRIP indication.
11.4.13.1

Function revision history

Document
revision
A
B
C
D
E
Table continues on next page
160
COMMON TRIP COMMAND (trip)
TRIPZ1 (tripZone1)
TRIPZ2 (tripZone2)
GENMODE (generatorMode)
MOTMODE (motorMode)
0.5
1
1.5
2
time in seconds
Boolean output signals for the injected current with two components: a 50 Hz current
component and a 49.5 Hz current component
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
© 2017 - 2021 Hitachi Power Grids. All rights reserved
START (start)
2.5
3
3.5
"Preparing the IED to verify
1MRK 504 165-UUS Rev. J
4
4.5
5
IEC10000142-1-en.vsd
settings".
GUID-A7F84AD6-F164-491B-B25E-D3BB002E1BDA v3
Transformer protection RET670
Commissioning manual
M13850-2 v9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret670

Table of Contents