Echoflex Installation Guide
Dual Tech Ceiling-mount Vacancy Sensor
DIP Switches
DIP switches on the sensor electronics provide for additional configuration
options including Use Custom Config, Vacancy Timeout, Enable/Disable
detection LEDs, PIR Only Mode, and the ability to restore the sensor to its
factory defaults.
Switch #
1
2
3 and 4
5
6
7
8
Dual Tech Ceiling-mount Vacancy Sensor
Unused (leave Off)
Enable/Disable Custom Config Mode
When "Custom Config" is set to Off (default), also known
•
as Basic configuration mode, the local DIP switch settings
for Vacancy Timeout, Enable PIR LED, and dual technology
features are used. See
When "Custom Config" is set to On, all other local DIP
•
switch settings are ignored. Instead, the settings made by
the ElahoAccess App are used.
Vacancy Timeout
5 min = Switches 3 and 4 are Off
•
15 min = Switch 3 is Off and Switch 4 is On (default)
•
30 min = Switch 3 is On and Switch 4 is Off
•
Auto = Both switches are On
•
Detection LEDs
When set to On (default), the occupancy detection LEDs
•
illuminate when movement is detected.
When set to Off, the occupancy detection LEDs are
•
disabled unless the unit is in Walk Test mode.
PIR Only Mode
When set to On, acoustic detection technology is disabled
•
for the sensor.
When set to Off (default), both PIR and acoustic detection
•
technologies are used by the sensor.
Unused (leave Off)
Restore to Defaults at boot
When set to On and power is cycled to the sensor, the
•
unit restores to its factory default settings.
Off is the default setting.
•
Use
Configuration on page 8
Page 7 of 12
.