ETC Installation Guide
Dual Tech Occupancy Sensor
DIP Switches
DIP switches on the sensor electronics provide for additional configuration
options including Use Custom Config, Vacancy Timeout, Enable/Disable
detection LEDs, PIR Only Mode, and the ability to restore the sensor to its
factory defaults.
Switch #
1
2
3 and 4
5
6
7
8
Dual Tech Occupancy Sensor
Unused (leave Off)
Enable/Disable Custom Config Mode
When "Custom Config" is set to Off (default), also known
•
as Basic configuration mode, the local DIP switch settings
for Vacancy Timeout, Enable PIR LED, and dual technology
features are used. Sensor actions can be adjusted using
the program [MODE] button. This is the default setting.
See
Configuration on page 8
When "Custom Config" is set to On, all other local DIP
•
switch settings are ignored. Instead, the settings made by
the EchoAccess App are used.
Vacancy Timeout
5 min = Switches 3 and 4 are Off
•
15 min = Switch 3 is Off and Switch 4 is On (default)
•
30 min = Switch 3 is On and Switch 4 is Off
•
Auto = Both switches are On
•
Detection LEDs
When set to On (default), the occupancy detection LEDs
•
illuminate when movement is detected.
When set to Off, the occupancy detection LEDs are
•
disabled unless the unit is in Walk Test mode.
PIR Only Mode
When set to On, acoustic detection technology is disabled
•
for the sensor.
When set to Off (default), both PIR and acoustic detection
•
technologies are used by the sensor.
Unused (leave Off)
Restore to Defaults at boot
When set to On and power is cycled to the sensor, the
•
unit restores to its factory default settings.
Off is the default setting.
•
Use
.
Page 7 of 12
ETC