IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-10
IEC 61000-4-11
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-18
RUGGEDCOM RST2228P
Installation Manual, 07/2021, C79000-G8976-1403-13
Test
Burst (Fast
Transient)
Surge
Induced
(Conducted) RFI
Magnetic Field
Damped
Oscillating
Magnetic Field
Voltage Dips
and Interrupts
Mains Frequency
Voltage
Ripple on DC
Power Supply
Damped
Oscillatory Wave
6.2 EMC and Environmental Type Tests
Description
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
PoE Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Enclosure Ports
Enclosure Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
DC Power Ports
Signal Ports
DC Power Ports
Certification
Test Levels
Severity Levels
± 4 kV at 2.5
and 5 kHz
± 4 kV at 2.5
and 5 kHz
± 4 kV at 2.5
and 5 kHz
± 4 kV at 5 kHz
± 4 kV Line-
to-Earth
± 2 kV Line-to-Line
± 2 kV Line-
to-Earth, ± 1
kV Line-to-Line
± 4 kV Line-
to-Earth
± 2 kV Line-to-Line
± 1 kV Line-
to-Earth
± 0.5 kV
Line-to-Line
10 V
10 V
10 V
10 V
100 A/m for 3 min
1000 A/m for 1 s
100 A/m for
1 s (100 kHz
and 1 MHz)
30% for 1 period
60% for 50 periods
100% for 5 periods
100% for
50 periods
30 V for 60 s
300 V for 1 s
30 V for 60 s
300 V for 1 s
30 V for 60 s
300 V for 1 s
15%
2.5 kV
Common Mode
2.5 kV
Common Mode
a
Note
4
4
4
4
3
4
2
3
3
3
3
5
5
 
4
4
4
3
3
3