Operation Notices - Gree XK86 Owner's Manual

Wired controller
Table of Contents

Advertisement

Wired Controller (XK86 and XE76-33/H)

2 Operation Notices

 The power supply for all indoor units must be unified.
 Prohibit installing the wired controller at wet or sunshine places.
 Do not knock, throw or frequently disassemble the wired controller.
 Do not operate the wired controller with wet hands.
 When the system mode priority is the master-slave mode, in one system network,
you must set one indoor unit as the master indoor unit, Other indoor units are slave
indoor units .
 When the system mode priority is the master-slave mode, the operation mode of
the system is basing on that of the master indoor unit. The master indoor unit can
be set to any mode (including auto mode), while the slave indoor unit can't set to
the mode that conflicts with the system mode.
 When the system mode priority is: Cooling mode is prioritized, heating mode is
prioritized, first-set mode is prioritized, or last-set mode is prioritized. The indoor
unit can be set to any mode (excluding auto mode). The indoor unit will
automatically switch to the system mode, when the operation mode of the indoor
unit conflicts with the system operation mode.
 When the system mode priority is the voting mode (indoor unit's capacity is
prioritized / number of indoor units is prioritized). The indoor unit can be set to any
mode (excluding the auto mode). The indoor unit will be stopped, when the
operation mode of the indoor unit conflicts with the system operation mode after
voting.
2