Crestron CLW-DIM1/4RF, -DIMS1/4RF, -SLVD1RF
Operations Guide - DOC. 6396
Network Device Tree with Devices Set Up with SMW Program Tree

Manually Setting the MNET ID in Crestron Toolbox

The following method permits you to change the MNET ID of any infiNET device
on the infiNET network through the "Network Device Tree" window.
This method does not change the MNET ID as assigned in SIMPL Windows. For
information on setting the MNET ID in SIMPL Windows, refer to "Setting the
MNET ID in Device Settings" on page 26. If MNET IDs have already been assigned
in a SIMPL Windows program, use the Touch Settable ID method described on page
12 to change the MNET ID to match the MNET ID specified in the SIMPL Windows
program.
NOTE: You may also use D3 Pro or SystemBuilder to perform MNET ID setup.
Refer to the respective help file for more information.
1. Open Crestron Toolbox and establish communications with the control
system (refer to "Establishing Communications" on page 28).
2. Use the Network Device Tree and connect to the control system to verify
that the gateway is connected to the control system and that all infiNET
devices are acquired on the gateway. infiNET devices with MNET ID 01
will be shown with a
infiNET Dimmers: Crestron CLW-DIM1/4RF, -DIMS1/4RF, -SLVD1RF • 19
infiNET™ Dimmers
icon as shown in the following diagram.