Remote Slab Sensor
Ensure that the sensor conduit is vertically centered in the slab below the
surface.
Sensor Conduit position in Slab
Sensor Position – Top View
Midway Between
Heating Elements
or Pipes
4 • Remote Slab Sensor: CHV-RSS
• In small rooms, position the sensor near the center of the floor.
• In larger rooms, ensure that the sensor is at least six feet from
the wall.
• In very large spaces, two sensors may be used to average the
floor temperature.
• The sensor should be placed midway between the heating
elements.
Floor
Crestron CHV-RSS
Sensor Conduit
Slab
Heating Cables or Pipes
Heating Pipe or
Elements
Conduit
Sensor
Center of Floor
(or 6 ft from wall
minimum in large
rooms)
Installation Guide – DOC. 6229A