Mandik alnor FDMD Manual page 10

Table of Contents

Advertisement

TPM 092/13
Fig. 9
Installation in a solid wall construction
2
1
Fig. 10 Installation in a solid wall construction
3
2
1
* Stuffing box and fire protection mastic can be replaced by another approved
fire sealing system for damper installation with equivalent material properties.
Fig. 11 Installation in a solid wall construction
3
2
1
1
1
1
10
2
POSITION
1
Fire damper FDMD
2
Mortar or gypsum with min.
density 800 kg/m
3
2
3
POSITION
1
Fire damper FDMD
2
Stuffing box (mineral stone wool
3
min. density 140 kg/m
)
3
Fire protection mastic min.
thickness 1 mm
Used materials - example*:
2
Promapyr, Rockwool Steprock HD
3
Promastop - P, K
2
3
POSITION
1
Fire damper FDMD
2
Fire resistant board
3
Fire stop coating thickness 1 mm
Used materials - example*:
2
Hilti CP673 PF
3
Hilti CP673