EDMT331529A
For residential indoor unit use
No.
1
Remote controller
Wireless
Note 2
2
Wiring adaptor for time clock/remote controller
(Normal open pulse contact/normal open contact)
3
Remote controller loss prevention chain
4
Interface adaptor for DIII-NET use
Notes:
1. A wireless remote controller is a standard accessory.
2. Time clock and other devices should be obtained locally.
1.2
System Configuration
No.
1
Residential central remote controller
2
Central remote controller
2-1
Electrical box with earth terminal (3 blocks)
3
Unified ON/OFF controller
3-1
Electrical box with earth terminal (2 blocks)
3-2
Noise filter (for electromagnetic interface use only)
4
Schedule timer
5-room centralized
5
controller for residential
indoor units
6
Interface adaptor for residential indoor units
7
Interface adaptor for SkyAir series
8
Central control adaptor kit
9
Wiring adaptor for other air-conditioner
10
DIII-NET Expander Adaptor
10-1 Mounting plate
Notes:
1. Installation box for adaptor must be obtained locally.
2. For residential use only. Cannot be used with other centralized control equipment.
3. A wiring adaptor (KRP413AB1S) is also required for each indoor unit.
4. No adaptor is required for some indoor units.
Option of Control
Item
Item
For C(F)DXS, FTXJ, FTXS
For UAT(Y)-K(A),FD-K
CDXS-EA
FDXS-C
KRP413AB1S
KKF917A4
KRP928BB2S
Model No.
Up to 16 groups of indoor units (128 units) can be easily
Note 2
controlled using the large LCD panel, ON/OFF, temperature
DCS303A51
settings and scheduling can be controlled individually for indoor
units.
Up to 64 groups of indoor units (128 units) can be connected,
DCS302CA61
and ON/OFF, temperature setting and monitoring can be
accomplished individually or simultaneously. Connectable up to
KJB311AA
2 controllers in one system.
DCS301BA61
Up to 16 groups of indoor units (128 units) can be turned, ON/
OFF individually or simultaneously, and operation and
KJB212AA
malfunction can be displayed. Can be used in combination with
up to 8 controllers.
KEK26-1A
Programmed time weekly schedule can be controlled by unified
DST301BA61
control for up to 64 groups of indoor units (128 units). Can turn
units ON/OFF twice per day.
Up to 5 indoor units can be controlled. This is a low cost system
Note 3
KRC72A
which can only control ON/OFF.
KRP928BB2S
Adaptors required to connect products other than those of the
Note 4
VRV system to the high-speed DIII-NET communication
DTA112BA51
system adopted for the VRV system.
To use any of the above optional controllers, an appropriate
DTA107A55
adaptor must be installed on the product unit to be controlled.
DTA103A51
Up to 1024 units can be centrally controlled in 64 different
groups.
DTA109A51
Wiring restrictions (max. length: 1,000m, total wiring length:
2,000m, max. number of branches: 16) apply to each adaptor.
Fixing plate for DTA109A51
KRP4A92
Option List of Controllers
Type
FTXS-D
FTXJ-N
FTXS-E
FTXS-F
— Note 1
KKF910A4
KKF917A4
Function
19