Specifications

1. Specifications
Ceiling suspended type
Model
Power supply
1 3 Cooling capacity
2 3 Heating capacity
Casing colour
Dimensions: (H×W×D)
Model
Type
Motor output ×
Number of units
Fan
Airflow rate (H/L)
Drive
Temperature control
Sound absorbing thermal insulation material
Air filter
Liquid pipes
Piping
Gas pipes
Connections
Drain pipe
Mass
4 Sound pressure level (H/L)
Safety devices
Refrigerant control
Standard accessories
Specification
Drawing No.
Sound level
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
212
FXHQ32MAVE
1 phase, 220-240/220V, 50/60Hz
kcal/h
3,100
Btu/h
12,300
kW
3.6
kcal/h
3,400
Btu/h
13,600
kW
4.0
White (10Y9/0.5)
mm
195×960×680
3D12K1AA1
Sirocco fan
W
62×1
m³/min
12/10
l/s
200/166
cfm
424/353
Direct drive
Microprocessor thermostat for cooling
and heating
Glass wool
Resin net (with mold resistant)
φ6.4 (Flare connection)
mm
φ12.7 (Flare connection)
mm
VP20
mm
(External dia. 26, Internal dia. 20)
kg
24
dB(A)
36/31
Fuse.
Thermal protector for fan motor.
Electronic expansion valve
Operation manual. Installation
manual. Drain hose. Paper pattern for
installation. Clamp metal. Insulation
for fitting. Clamps. Washers.
C: 3D038815A
C: 4D035301
FXHQ63MAVE
1 phase, 220-240/220V, 50/60Hz
6,100
24,200
7.1
6,900
27,300
8.0
White (10Y9/0.5)
195×1,160×680
4D12K1AA1
Sirocco fan
62×1
17.5/14
291/233
618/494
Direct drive
Microprocessor thermostat for cooling
and heating
Glass wool
Resin net (with mold resistant)
φ9.5 (Flare connection)
φ15.9 (Flare connection)
VP20
(External dia. 26, Internal dia. 20)
28
39/34
Fuse.
Thermal protector for fan motor.
Electronic expansion valve
Operation manual. Installation
manual. Drain hose. Paper pattern for
installation. Clamp metal. Insulation
for fitting. Clamps. Washers.
C: 3D038815A
C: 4D035302
EDMT331529A
FXHQ100MAVE
1 phase, 220-240/220V, 50/60Hz
9,600
38,200
11.2
10,800
42,700
12.5
White (10Y9/0.5)
195×1,400×680
3D12K2AA1
Sirocco fan
130×1
25/19.5
416/325
883/688
Direct drive
Microprocessor thermostat for cooling
and heating
Glass wool
Resin net (with mold resistant)
φ9.5 (Flare connection)
φ15.9 (Flare connection)
VP20
(External dia. 26, Internal dia. 20)
33
45/37
Fuse.
Thermal protector for fan motor.
Electronic expansion valve
Operation manual. Installation
manual. Drain hose. Paper pattern for
installation. Clamp metal. Insulation
for fitting. Clamps. Washers.
C: 3D038815A
C: 4D035303A
Conversion formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
l/s=m³/min×1000/60
FXHQ-MA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxymq4-6aveRxymq8ay1Rxymq9ay1

Table of Contents