Daikin VRV IV S Series Engineering Data page 231

50 hz
Hide thumbs Also See for VRV IV S Series:
Table of Contents

Advertisement

EDMT331529A
Wall mounted type
Model
Power supply
1 3 Cooling capacity
2 3 Heating capacity
Casing colour
Dimensions: (H×W×D)
Model
Type
Motor output ×
Number of units
Fan
Airflow rate (H/L)
Drive
Temperature control
Sound absorbing thermal insulation material
Air filter
Liquid pipes
Piping
Gas pipes
connections
Drain pipe
Mass
4 Sound pressure level (H/L)
Safety devices
Refrigerant control
Standard accessories
Specification
Drawing No.
Sound level
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
FXAQ-P
FXAQ40PVE
1 phase, 220-240/220V, 50/60Hz
kcal/h
3,900
Btu/h
15,400
kW
4.5
kcal/h
4,300
Btu/h
17,100
kW
5.0
White (3.0Y8.5/0.5)
mm
290×1,050×238
QCL9686M
Cross flow fan
W
43×1
m³/min
12/9
l/s
200/150
cfm
424/318
Direct drive
Microprocessor thermostat for
cooling and heating
Foamed polystyrene /
Foamed polyethylene
Resin net (Washable)
φ6.4 (Flare connection)
mm
φ12.7 (Flare connection)
mm
VP13
mm
(External dia. 18, Internal dia. 13)
kg
14
dB(A)
39/34
Fuse
Electronic expansion valve
Operation manual. Installation
manual. Installation panel. Paper
pattern for installation. Insulation tape.
Clamps. Screws.
C: 3D077064A
C: 4D077093
FXAQ50PVE
1 phase, 220-240/220V, 50/60Hz
4,800
19,100
5.6
5,400
21,500
6.3
White (3.0Y8.5/0.5)
290×1,050×238
QCL9686M
Cross flow fan
43×1
15/12
250/200
530/424
Direct drive
Microprocessor thermostat for
cooling and heating
Foamed polystyrene /
Foamed polyethylene
Resin net (Washable)
φ6.4 (Flare connection)
φ12.7 (Flare connection)
VP13
(External dia. 18, Internal dia. 13)
14
42/37
Fuse
Electronic expansion valve
Operation manual. Installation
manual. Installation panel. Paper
pattern for installation. Insulation tape.
Clamps. Screws.
C: 3D077064A
C: 4D077094
Specifications
FXAQ63PVE
1 phase, 220-240/220V, 50/60Hz
6,100
24,200
7.1
6,900
27,300
8.0
White (3.0Y8.5/0.5)
290×1,050×238
QCL9686M
Cross flow fan
43×1
19/14
316/233
671/494
Direct drive
Microprocessor thermostat for
cooling and heating
Foamed polystyrene /
Foamed polyethylene
Resin net (Washable)
φ9.5 (Flare connection)
φ15.9 (Flare connection)
VP13
(External dia. 18, Internal dia. 13)
14
47/41
Fuse
Electronic expansion valve
Operation manual. Installation
manual. Installation panel. Paper
pattern for installation. Insulation tape.
Clamps. Screws.
C: 3D077064A
C: 4D077095
Conversion formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
l/s=m³/min×1000/60
229
12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxymq4-6aveRxymq8ay1Rxymq9ay1

Table of Contents