Correction Factor For Te: 9°C - Daikin VRV IV S Series Engineering Data

50 hz
Hide thumbs Also See for VRV IV S Series:
Table of Contents

Advertisement

Capacity Tables
7.3
Correction Factor for Te: 9°C
TC
FXCQ20MVE
SHF
TC
FXCQ25MVE
SHF
TC
FXCQ32MVE
SHF
TC
FXCQ40MVE
SHF
TC
FXCQ50MVE
SHF
TC
FXCQ63MVE
SHF
TC
FXCQ80MVE
SHF
TC
FXCQ125MVE
SHF
106
14°CWB
16°CWB
20°CDB
23°CDB
0.667
0.697
1.172
1.184
0.681
0.690
1.147
1.192
0.681
0.690
1.147
1.192
0.671
0.687
1.167
1.191
0.663
0.690
1.177
1.185
0.682
0.692
1.144
1.191
0.707
0.689
1.166
1.187
0.683
0.691
1.132
1.180
VRV (Te: 9°C)
18°CWB
19°CWB
26°CDB
27°CDB
0.748
0.767
1.130
1.106
0.741
0.766
1.135
1.108
0.741
0.766
1.135
1.108
0.748
0.772
1.128
1.101
0.753
0.777
1.123
1.097
0.740
0.763
1.138
1.111
0.752
0.776
1.124
1.098
0.753
0.776
1.121
1.096
EDMT331529A
When a mixed combination of VRV and
residential indoor units is connected
20°CWB
22°CWB
28°CDB
30°CDB
0.788
0.817
1.084
1.061
0.787
0.817
1.086
1.061
0.787
0.817
1.086
1.061
0.792
0.821
1.082
1.059
0.795
0.831
1.081
1.054
0.784
0.815
1.088
1.061
0.795
0.830
1.080
1.055
0.796
0.831
1.077
1.054
24°CWB
32°CDB
0.844
1.039
0.842
1.041
0.842
1.041
0.854
1.035
0.857
1.034
0.840
1.042
0.856
1.035
0.855
1.043
FXCQ-M

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxymq4-6aveRxymq8ay1Rxymq9ay1

Table of Contents