Daikin VRV IV S Series Engineering Data page 361

50 hz
Hide thumbs Also See for VRV IV S Series:
Table of Contents

Advertisement

EDMT331529A
Installation of the Unit
6) Attach the printed circuit board and electrical equipment
cover to the other side and secure with the screws.
2.
Ceiling-suspended type
Procedure:
1) Fix the furnished hanger metal
(4 locations in total)
2) Using an insert-hole-in-anchor, hang the hanging bolt.
3) Install a hexagon nut and a flat washer (field supply) to
the hanging bolt as shown in the figure in the below,
and lift the unit to hang on the hanger metal.
4) After checking with a level that the unit is level, tighten
the hexagon nut.
* The tilt of the unit should be within ±5° in front/ back
and left/right.
3.
Wall-mounted type
Procedure:
1) Fix the furnished hanger metal
(4 locations in total)
2) Create a gap with the wall and screw in the temporary
screws, and hang the BP unit.
3) After checking with a level that the unit is level, fix the
unit with screws (M5, field supply).
* The tilt of the unit should be within ±5° in front/ back
and left/right.
CAUTION
• Be sure to install the unit with the top surface up.
• Do not install near bedrooms. The sound of refrigerant
flowing through the piping may sometimes be audible.
8
BP Units
Hanger metal 7
with two screws
.
7
8
Flat washer
Nut
Hanger metal 7
BP unit
Hanging bolt
Screws 8
with two screws
.
7
8
Screws 8
Temporary screw:
Screw in temporarily after
opening a slight gap with
the wall.
Temporary screws:
attach and then hang the
unit on them. (2 screws)
: screw for fixing. (4 places)
Printed circuit board
Electrical
Top surface of the unit
equipment
cover
Insert the
tabs fully.
Hanging bolt (M10 or M8)
Six-sided nut (M10 or M8)
Flat washer
Hanger metal 7
Hanger
metal 7
Screws (M5)
(field supply)
Installation
Screws 8
Ceiling side
Screws (M5)
(field supply)
English
3P155399-1E
359
16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxymq4-6aveRxymq8ay1Rxymq9ay1

Table of Contents