Specifications - Daikin VRV IV S Series Engineering Data

50 hz
Hide thumbs Also See for VRV IV S Series:
Table of Contents

Advertisement

Specifications

1. Specifications
Wall mounted type
Model
Power supply
1 3 Cooling capacity
2 3 Heating capacity
Casing colour
Dimensions: (H×W×D)
Model
Type
Motor output ×
Number of units
Fan
Airflow rate (H/L)
Drive
Temperature control
Sound absorbing thermal insulation material
Air filter
Liquid pipes
Piping
Gas pipes
connections
Drain pipe
Mass
4 Sound pressure level (H/L)
Safety devices
Refrigerant control
Standard accessories
Specification
Drawing No.
Sound level
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
228
FXAQ20PVE
1 phase, 220-240/220V, 50/60Hz
kcal/h
1,900
Btu/h
7,500
kW
2.2
kcal/h
2,200
Btu/h
8,500
kW
2.5
White (3.0Y8.5/0.5)
mm
290×795×238
QCL9661M
Cross flow fan
W
40×1
m³/min
7.5/4.5
l/s
125/75
cfm
265/159
Direct drive
Microprocessor thermostat for
cooling and heating
Foamed polystyrene /
Foamed polyethylene
Resin net (Washable)
φ6.4 (Flare connection)
mm
φ12.7 (Flare connection)
mm
VP13
mm
(External dia. 18, Internal dia. 13)
kg
11
dB(A)
35/31
Fuse
Electronic expansion valve
Operation manual. Installation
manual. Installation panel. Paper
pattern for installation. Insulation tape.
Clamps. Screws.
C: 3D077064A
C: 4D077090
FXAQ25PVE
1 phase, 220-240/220V, 50/60Hz
2,400
9,600
2.8
2,800
10,900
3.2
White (3.0Y8.5/0.5)
290×795×238
QCL9661M
Cross flow fan
40×1
8/5
133/83
282/177
Direct drive
Microprocessor thermostat for
cooling and heating
Foamed polystyrene /
Foamed polyethylene
Resin net (Washable)
φ6.4 (Flare connection)
φ12.7 (Flare connection)
VP13
(External dia. 18, Internal dia. 13)
11
36/31
Fuse
Electronic expansion valve
Operation manual. Installation
manual. Installation panel. Paper
pattern for installation. Insulation tape.
Clamps. Screws.
C: 3D077064A
C: 4D077091
EDMT331529A
FXAQ32PVE
1 phase, 220-240/220V, 50/60Hz
3,100
12,300
3.6
3,400
13,600
4.0
White (3.0Y8.5/0.5)
290×795×238
QCL9661M
Cross flow fan
40×1
8.5/5.5
142/91
300/194
Direct drive
Microprocessor thermostat for
cooling and heating
Foamed polystyrene /
Foamed polyethylene
Resin net (Washable)
φ6.4 (Flare connection)
φ12.7 (Flare connection)
VP13
(External dia. 18, Internal dia. 13)
11
38/31
Fuse
Electronic expansion valve
Operation manual. Installation
manual. Installation panel. Paper
pattern for installation. Insulation tape.
Clamps. Screws.
C: 3D077064A
C: 4D077092
Conversion formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
l/s=m³/min×1000/60
FXAQ-P

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxymq4-6aveRxymq8ay1Rxymq9ay1

Table of Contents