Capacity Tables; Cooling Capacity; Heating Capacity - Daikin VRV IV S Series Engineering Data

50 hz
Hide thumbs Also See for VRV IV S Series:
Table of Contents

Advertisement

EDMT331529A

7. Capacity Tables

7.1

Cooling Capacity

14.0°CWB
Capacity
Model
indication
20°CDB
TC
FXZQ20MVE
20
1.5
FXZQ25MVE
25
1.9
FXZQ32MVE
32
2.4
FXZQ40MVE
40
3.0
FXZQ50MVE
50
3.8
TC:
Total capacity: kW
SHC: Sensible heat capacity: kW
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2.
shows rated condition.
7.2

Heating Capacity

Capacity
Model
indication
FXZQ20MVE
20
FXZQ25MVE
25
FXZQ32MVE
32
FXZQ40MVE
40
FXZQ50MVE
50
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2.
shows rated condition.
FXZQ-M
16.0°CWB
18.0°CWB
23°CDB
26°CDB
SHC
TC
SHC
TC
1.3
1.8
1.5
2.1
1.5
2.3
1.8
2.6
1.9
2.9
2.1
3.4
2.5
3.6
2.9
4.2
3.1
4.5
3.6
5.2
16.0
18.0
kW
kW
2.6
2.6
3.4
3.4
4.2
4.2
5.2
5.2
6.6
6.6
Indoor air temp.
19.0°CWB
20.0°CWB
27°CDB
28°CDB
SHC
TC
SHC
TC
1.7
2.2
1.7
2.2
2.0
2.8
2.0
2.8
2.4
3.6
2.4
3.6
3.2
4.5
3.3
4.6
4.0
5.6
4.1
5.7
Indoor air temp. °CDB
20.0
21.0
kW
kW
2.5
2.4
3.2
3.1
4.0
3.9
5.0
4.8
6.3
6.1
Capacity Tables
22.0°CWB
24.0°CWB
30°CDB
32°CDB
SHC
TC
SHC
TC
1.6
2.3
1.5
2.3
1.9
2.9
1.8
3.0
2.2
3.7
2.2
3.8
3.2
4.7
3.1
4.8
4.1
5.8
3.9
5.9
22.0
24.0
kW
kW
2.3
2.2
3.0
2.8
3.7
3.5
4.7
4.4
5.9
5.5
SHC
1.4
1.7
2.1
4
2.9
3.7
69