Fixture Linking

You will need a serial data link to run light shows of one or more fixtures using a DMX-512 controller
or to run synchronized shows on two or more fixtures set to a master/slave operating mode. The
combined number of channels required by all the fixtures on a serial data link determines the number
of fixtures the data link can support.
Important:
Maximum recommended serial data link distance: 500 meters (1640 ft.)
Maximum recommended number of fixtures on a serial data link: 32 fixtures

Data Cabling

To link fixtures together you must obtain data cables. You can purchase CHAUVET-certified DMX
cables directly from a dealer/distributor or construct your own cable. If you choose to create your own
cable please use data-grade cables that can carry a high quality signal and are less prone to
electromagnetic interference.

DMX DATA CABLE

Use a Belden© 9841 or equivalent cable which meets the specifications for EIA RS-485 applications.
Standard microphone cables cannot transmit DMX data reliably over long distances. The cable will
have the following characteristics:

CABLE CONNECTORS

Cabling must have a male XLR connector on one end and a female XLR connector on the other end.
DMX connector configuration
INPUT
CAUTION
COLORado™ Batten 80i User Manual
Fixtures on a serial data link must be daisy chained in one single line. To comply with the EIA-
485 standard no more than 32 devices should be connected on one data link. Connecting more
than 32 fixtures on one serial data link without the use of a DMX optically-isolated splitter may
result in deterioration of the digital DMX signal.
2-conductor twisted pair plus a shield
Maximum capacitance between conductors – 30 pF/ft.
Maximum capacitance between conductor and shield – 55 pF/ft.
Maximum resistance of 20 ohms / 1000 ft.
Nominal impedance 100 – 140 ohms
COMMON
1
DMX +
3
2
-
DMX
Do not allow contact between the common and the fixture's chassis ground. Grounding the common
can cause a ground loop, and your fixture may perform erratically. Test cables with an ohm meter to
verify correct polarity and to make sure the pins are not grounded or shorted to the shield or each othe
1
3
2
1
OUTPUT
3
Termination reduces signal errors. To
2
avoid signal transmission problems
and interference, it is always
advisable to connect a DMX signal
terminator.
12
Resistance 120
ohm 1/4w
between pin 2
(DMX -) and pin
3 (DMX +) of the
last fixture.
r.
5/19/2008 10:40 AM