2.2.2

Scope of the power supply for the transmission cable

To implement the AnyWire Bitty system, all conditions specified by the following calculation formulas 1) to 3) have to
be met.
Item
Calculation formula 1)
Calculation formula 2)
Calculation formula 3)
(1) Description of calculation formula 1)
(a) Related constant of non-isolated slave modules (Ihin, Iho)
For non-isolated slave modules, current required for the internal control circuit and connected load is supplied
through the transmission cable (DP, DN).
Ihin(A)
= Current consumption of non-isolated input slave module/I/O combined slave module
= Current consumption of non-isolated input slave module/I/O combined slave module + Current consumption
of connected load (three-wire sensor)  Number of points
Iho(A)
= Current consumption of non-isolated output slave module
= Current consumption of non-isolated output slave module + Current consumption of connected load 
Number of points
24V 0V
24V 0V
24VDC external
power supply
● The 24VL and 0VL terminals of a slave module are used to supply the power to the connected load. For details, refer to
the manual for the slave module used.
● For the current consumption of non-isolated slave modules, refer to the manual for the slave module used.
16
I(A) = (Ihin  m) + (Iho  n) + (Izdin  p) + (Izdo  q)  The maximum value of the transmission cable supply current
The number of connected modules by type: m, n, p, q
Vm(V) - V(V)  20V
Vm(V) - V(V)  The lowest limit of the allowable voltage range for connected load
NZ2AW1C1BY
DN DP
Description
Non-isolated slave module
Control circuit
Power supply
generation
DN DP
24VL
0VL
0
Connected load
1
n