(3) Power supply module
Use a CE-marked external power supply and ground the FG terminal.
(External power supply used for the tests conducted by Mitsubishi: PS5R-SF24 made by IDEC Corporation)
(4) Installation environment
Use this product in Zone A
*1
Zone means a category determined according to the industrial environment conditions and defined by the harmonized
standard EN61131-2 of the EMC and Low Voltage Directives.
Zone C: Main power supply insulated from the public power supply by a special transformer
Zone B: Special power supply with the secondary surge protector from the main power (Rated voltage is assumed to be
300V or less.)
Zone A: Local power supply protected by an AC-DC converter or an insulating transformer from the special power
supply (Rated voltage is assumed to be 120V or less.)
Appendix 1.2
The Low Voltage Directive does not apply to this product because it operates on 24VDC power supply.
For making the PLC system used comply with the Low Voltage Directive, refer to the section about the EMC and Low
Voltage Directives in the user's manual of the CPU module to be used.