2.2

Performance Specifications

2.2.1
Performance specifications
Classification
Station type
CC-Link version
Communication speed
Number of occupied stations
CC-Link side
Number of connectable
modules
Connection location of
NZ2AW1C1BY
Connection cable
Transmission clock
Maximum transmission
distance (total length)
Number of connectable
slave modules
Transmission system
Connection type
Transmission protocol
Error control
Number of connected I/O
points
AnyWire Bitty side
RAS function
Transmission cable (DP,
*2
DN)
Power cable (24V, 0V)
Maximum number of writes
to EEPROM
Power supply
Common
External dimensions
Weight
14
Item
Remote device station
Ver. 1.10
10M/5M/2.5M/625K/156Kbps (switching by transmission speed setting switch)
Remote device stations 1 to 4 are occupied according to the setting of the specification
selection switch.
1 station (RX/RY number of occupied points: 32 points) (RWr/RWw 4/4)
2 stations (RX/RY number of occupied points: 64 points) (RWr/RWw 8/8)
3 stations (RX/RY number of occupied points: 96 points) (RWr/RWw 12/12)
4 stations (RX/RY number of occupied points: 128 points) (RWr/RWw 16/16)
Up to 42
No restriction
CC-Link dedicated cable/High-performance CC-Link dedicated cable/
*1
Ver.1.10- compatible CC-Link dedicated cable
27.0kHz
100m
*2
Up to 128 (varies depending on the current consumption of each slave module)
DC power supply transmission total frame cyclic system
Bus topology (multidrop system, T-branch system, tree branch system)
Dedicated protocol (AnyWire Bitty)
Double-check system
Up to 512 points (256 input points/256 output points)
Disconnected transmission cable location detection function, transmission cable short
detection function, transmission cable voltage drop detection function
• UL-compliant general-purpose 2-wire cable (VCTF, VCF 1.25, 0.75,
temperature rating 70 or higher)
• UL-compliant general-purpose wire (1.25, 0.75, temperature rating 70 or
higher)
• UL-compliant general-purpose 2-wire cable (VCTF, VCT 0.75 to 2.0,
temperature rating 70 or higher)
• UL-compliant general-purpose wire (0.75 to 2.0, temperature rating 70 or
higher)
Up to 100000 times
21.6 to 27.6VDC (24VDC -10 to +15%), ripple voltage 0.5Vp-p or lower
Voltage
Recommended voltage 26.4V (24VDC +10%)
Module current consumption: 0.2[A] (When 128 slave modules are connected, the
load current is not included.)
Current
Transmission cable supply current: Up to 2[A]
100mm (H)  40mm (W)  66mm (D)
0.16kg