Installation; Detector Positioning; Detector Orientation - UTC Fire and Security Det-Tronics X9800 Instructions Manual

Ir flame detector with pulse output x9800
Hide thumbs Also See for Det-Tronics X9800:
Table of Contents

Advertisement

INSTallaTION

The recommended lubricant for threads and
O-rings is a silicone free grease (part number
005003-001) available from Detector Electronics.
Under no circumstances should a lubricant
containing silicone be used.

DETECTOR pOSITIONING

Detectors should be positioned to provide the best
unobstructed view of the area to be protected. The
following factors should also be taken into consideration:
Identify all high risk fire ignition sources.
Be sure that enough detectors are used to adequately
cover the hazardous area.
Be sure that the unit is easily accessible for cleaning
and other periodic servicing.
Locate and position the detector so that the fire
hazard(s) are within both the field of view and
detection range of the device. Refer to Appendix A
for specific information.
• The detector should be aimed downward at least
10 to 20 degrees to allow lens openings to drain.
See Figure 1. The detector should be positioned
so that its field of view does not cover areas
outside the hazardous area. This will minimize
the possibility of false alarms caused by activities
outside the area requiring protection.
For best performance, the detector should be
mounted on a rigid surface in a low vibration area.
Dense fog, rain, as well as certain gases and vapors
can absorb IR radiation and reduce the sensitivity of
the detector.
Verify that all detectors in the system are properly
aimed at the area to be protected. (The Det-Tronics
Q1201C Laser Aimer is recommended for this
purpose.)
If possible, fire tests should be conducted to verify
correct detector positioning and coverage.
For ATEX installations, the X9800 detector housing
must be electrically connected to earth ground.
4.3
NOTE
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
NOTE: DETECTOR MUST ALWAYS BE AIMED
DOWNWARD AT LEAST 10 TO 20 DEGREES.
Figure 1—Detector Orientation Relative to Horizon

DETECTOR ORIENTATION

Refer to Figure 2 and ensure that the o i plate will be
oriented as shown when the X9800 is mounted and
sighted.
This will ensure proper operation of the
o i system and will also minimize the accumulation of
moisture and contaminants between the o i plate and the
viewing windows.
The o i plate must be securely tightened to ensure
proper operation of the o i system (40 oz./inches
recommended).
A2174
Figure 2—Front View of the X9800
6
INCORRECT
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
CORRECT
IMPORTANT
o i
PLATE
PLACE MAGNET
HERE TO INITIATE
MAGNETIC
IR VIEWING WINDOW
o i
MAGNET
DETECTOR STATUS INDICATOR
B1974
o i
95-8555

Advertisement

Table of Contents
loading

Table of Contents