En: Installation Sheet; Mounting The Unit; Connecting The Unit - UTC Fire and Security interlogix DI601AM Installation Sheet

Outdoor pir/am detector
Table of Contents

Advertisement

EN: Installation Sheet

Package
The package contains:
•1 x DI601AM
•1 x drilling template for fixing holes
•3 x 31.75 mm / 1.25 in. wall plugs
•3 x 31.75 mm / 1.25 in. screws
•1 x lens mask
•2 x additional curtain shutters
•1 x tamper cup
•2 x tamper caps (different lengths)
•1 x plastic locking tool
•1 x installation sheet
•1 x front cover screw cap
Introduction
The DI601AM Outdoor PIR/AM Detector is an external motion
detector and alarm trigger that uses two independent passive
infrared detectors.
Both sensors must trigger to cause the detector to signal an
alarm. The DI601AM uses quad PIR technology to deliver
precise, reliable presence detection.
Programmable options include a variable pulse count and a
choice of three detection ranges: 10 m, 20 m and 30 m.

Mounting the unit

When positioning the detector please consider that he PIR
sensor is more sensitive to a movement across the beams, and
less sensitive to a movement directly towards or away from the
beams.
During installation, protect the electronics against water, as
trapped moisture can affect or damage the unit.
We recommend that the cable entry and screw mounting holes
be sealed from within the detector using acrylic (non-silicone
based) sealants.
Note:
When locating the detector, please ensure the detector's
field of view is unobstructed.
To mount the detector:
1.Drill the wall to accept the fixing screws, the cable entry, and
the tamper cup (if used). See Figures 1 and 3.
A hole-drilling template is provided.
Notes
•Leave a minimum 10 cm (4 inches) clearance above the top of
the detector housing to allow the cover and the detector to be
positioned correctly.
•We recommend using the tamper cup on uneven wall surfaces.
•The recommended optimum mounting height for the detector is
3 m. Whilst it is possible to mount the unit higher, this will give
a reduced detection range and will require the detection subject
to move further through the already reduced detection area
before activation is signaled.
2.Remove the cover assembly by loosening the locking screw.
Squeeze the sides of the front cover to release the internal
catches.
The cover hinges from the top and lifts out of the location slot.
See Figure 2.
3.Use a razor knife to open a rubber seal to allow the cabling
into the unit (see Figure 4). Feed standard eight-core or 12-core
alarm cable though the wall and directly into the cable entry.
Bare the wires and connect to the top PCB terminal block
(Figure 15)
Caution:
Do not allow the cable to be trapped between the
rear gasket and the mounting surface as this may cause water
ingress. For surface mount cables use the conduit knock-out at
the bottom of the detector. Refer Fig 1 for good and bad cable
routings.
4.Screw the unit to the wall ensuring that the tamper pin is
correctly located and that the tamper micro-switch is closed.
Always ensure the detector base is screwed tightly to the wall
so that the tamper foot is pushed into the rear rubber gasket.
On uneven surfaces use the tamper cup and locate the tamper
foot into the cup. Drilling template is provided.
To aid installation, two spare tamper feet are provided. One
is 1 mm shorter and the other is 1 mm longer than the tamper
foot originally fitted. The tamper foot is a push fit and can be
removed by carefully pulling it from the pin. See Figure 1.
5.When the detector is aligned, connected, and programmed to
suit the installation:
a.Fit the cover to the detector base.
b.Lightly screw the locking screw.
c.Put the top of the locking tool into the small notch on each
side of the cover, and then apply slight pressure until the cover
locks into the base, as shown in Figure 5.
d.Tighten the locking screw.

Connecting the unit

The DI601AM includes jumpers that let you configure internal
Triple End-of-Line (TEOL) resistor values, when TEOL resistors
are required. Values are: 1, 2.2, 3.3, 4.7, 5.6, and 6.8 kΩ for
Alarm and Tamper (DEOL resistors). The values are 2.2, 3.3,
4.7, 5.6 and 10kΩ for Fault/Anti-Mask. Figure 15 shows:
1.TEOL resistor jumpers
2.Wiring points
3.TEOL enable used in conjunction with a jumper at the
required resistance
Alternatively, you can remove the jumpers and connect a
discrete resistor directly to the alarm, tamper or Fault/Anti-Mask
outputs as specified by third-party equipment.
The wiring schematic in Figure 15 shows how to connect and
the table in figure 16 shows how to calculate DEOL and TEOL
values with examples.
Table 1: Connections
Terminal
1
LED
2
TEST
3, 4
FAULT/MASK
Label
Description
Remote LED
enable
Remote TEST
input
Fault/Anti-Mask
relay normally
closed

Advertisement

Table of Contents
loading

Table of Contents