UTC Fire and Security Det-Tronics X9800 Instructions Manual page 11

Ir flame detector with pulse output x9800
Hide thumbs Also See for Det-Tronics X9800:
Table of Contents

Advertisement

#2
#1
X9800
#19
#22
DETECTOR 1
#2
#1
X9800
#19
#22
DETECTOR 2
#2
#1
X9800
#19
#22
DETECTOR 3
#2
#1
X9800
#19
#22
DETECTOR 4
#2
#1
X9800
#19
#22
DETECTOR 5
#2
#1
X9800
#19
#22
DETECTOR 6
#2
#1
X9800
#19
#22
DETECTOR 7
#2
#1
X9800
#19
#22
DETECTOR 8
TERMINAL IDENTIFICATION FOR X9800
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
o i
22
("D" LEAD)
4.3
NOTE: DO NOT CONNECT THE X9800 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
24
VDC
#2
+
#1
#19
#22
#2
#1
#19
J1-5
#22
J1-13
#2
#1
#19
J1-6
#22
J1-14
#2
#1
#19
J1-7
#22
J1-15
#2
#1
#19
J1-8
#22
J1-16
#2
#1
#19
J1-9
#22
J1-17
#2
#1
#19
J1-10
#22
J1-18
#2
#1
#19
J1-11
#22
J1-19
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
Figure 6—A Typical System, X9800 Detectors Wired to R7404 Controller
J1
R7404 CONTROLLER
1
+
}
10 TO 38 VDC
2
3
(A) +290 VDC
4
B - INPUT 1
5
B - INPUT 2
6
B - INPUT 3
7
B - INPUT 4
8
B - INPUT 5
9
B - INPUT 6
10
B - INPUT 7
11
B - INPUT 8
12
D1-1 o i DRIVER
EXTERNAL RESET/INHIBIT
13
D1-2 o i DRIVER
14
D1-3 o i DRIVER
15
D1-4 o i DRIVER
16
D1-5 o i DRIVER
STATUS & DET. OUTPUT S1
17
D1-6 o i DRIVER
STATUS & DET. OUTPUT S2
18
D1-7 o i DRIVER
STATUS & DET. OUTPUT S3
19
D1-8 o i DRIVER
STATUS & DET. OUTPUT S4
20
D2-1 o i DRIVER
STATUS & DET. OUTPUT S5
21
D2-2 o i DRIVER
STATUS & DET. OUTPUT S6
22
D2-3 o i DRIVER
STATUS & DET. OUTPUT S7
23
D2-4 o i DRIVER
STATUS & DET. OUTPUT S8
24
D2-5 o i DRIVER
25
D2-6 o i DRIVER
26
D2-7 o i DRIVER
27
D2-8 o i DRIVER
28
DMA OUT AVAILABLE
29
DMA OUT
30
DMA IN
31
DATA STROBE
32
CHASSIS (EARTH) GND
DMA IN AVAILABLE
9
J2
ZONE OUTPUT 1
33
ZONE OUTPUT 2
34
ZONE OUTPUT 3
35
ZONE OUTPUT 4
36
ZONE OUTPUT 5
37
ZONE OUTPUT 6
38
ZONE OUTPUT 7
39
ZONE OUTPUT 8
40
FIRE LOGIC "A"
41
FIRE LOGIC "B"
42
ALARM OUTPUT
43
44
OUTPUTS INHIBITED
45
FAULT OUTPUT
46
EXTERNAL ACCEPT
47
48
49
50
51
52
53
54
55
DATA BUS 0
56
DATA BUS 1
57
DATA BUS 2
58
DATA BUS 3
59
DATA BUS 4
60
DATA BUS 5
61
DATA BUS 6
62
DATA BUS 7
63
64
A2182
TO J1-2
62
0.47 μF / 400 VDC
NON-POLARIZED
63
64
GROUND FAULT PROTECTED SYSTEMS
95-8555