E+E Elektronik EE895 User Manual page 21

Miniature sensor module for co2 , temperature and barometric pressure
Hide thumbs Also See for EE895:
Table of Contents

Advertisement

6
Packet Format for Write Multiple Function Code 0x10
Request:
Modbus
Function
Address
Code
YY
10
Response from the E+E Modbus device:
Modbus
Address
YY
The supported addresses can be found in the datasheet and in the user manual of the specific E+E
device.
7
Data Encoding of Float Values
The Modbus standard allows for flexible word order, values larger than 16 bits, such as floating point
values (32 Bit).
7.1
IEEE 754 Format
The IEEE standard definition of floating point values:
SEEEEEEE
Byte 1
S ... Sign
E ... Exponent
M ... 23 Bit Mantissa
7.2
Modbus Floating Point Format
E+E devices use the Modbus floating point format. The byte pairs 1, 2 and 3, 4 are inverted as follows.
SEEEEEEE
Byte 3
User Manual EE895 Miniature Sensor Module for CO
Communication
Address
HB
LB
YY
YY
Communication Address
Function
Code
HB
10
YY
EMMMMMMM
Byte 2
EMMMMMMM
Byte 4
, T and p
2
Qunatity of
Byte
Registers
Count
HB
LB
YY
YY
YY
Quantity of Registers
LB
HB
YY
YY
MMMMMMMM
Byte 3
MMMMMMMM
Byte 1
N * Register
CRC
Values
HB
LB
LB
YY
YY
CC
CRC
LB
LB
YY
CC
MMMMMMMM
Byte 4
MMMMMMMM
Byte 2
HB
CC
HB
CC
21