Uart Interface; Modbus Protocol Over Uart Interface; Modbus Register Map - E+E Elektronik EE895 User Manual

Miniature sensor module for co2 , temperature and barometric pressure
Hide thumbs Also See for EE895:
Table of Contents

Advertisement

4.2

UART Interface

4.2.1

Modbus Protocol Over UART Interface

Modbus slave address: 0x5F
The interface settings are: Baud rate 9600, 8 Data, No parity, 1 Stop bit (9600 8 N 1)
The slave address and the interface settings are fixed, they cannot be changed by the user.
The EE895 module shall be addressed according to the specification "Modbus over serial line V1.02",
see
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
Modbus frame description (screenshot taken from the "Modbus over serial line Specification and Imple-
mentation Guide V1.02" mentioned above):
4.3

Modbus Register Map

Following Modbus register map is valid for both, the I
saved as 32 bit floating point values (data type FLOAT) and as 16 bit signed integer values (data type
INTEGER), please refer to Tab. 9 and Tab. 10 below:
FLOAT 32 bit
Parameter
Read register: function code 0x03
Temperature T
Temperature T
Temperature T
CO
(average)
2
CO
(raw)
2
Pressure p
Pressure p
1) Register number starts from 1
2) Register address starts from 0
Tab. 9 I
C and UART Modbus register map for 32 bit floating point values
2
14
C and the UART interface. The measured data is
2
Unit
Register number
° C
1003
° F
1005
K
1009
ppm
1061
ppm
1063
mbar
1201
psi
1203
User Manual EE895 Miniature Sensor Module for CO
.
[DEC]
Register address
1)
2)
0x3EA
0x3EC
0x3F0
0x424
0x426
0x4B0
0x4B2
[HEX]
, T and p
2

Advertisement

Table of Contents