Layout of the installation

This photo shows the final installation with component placing dimensions in
millimetres and (inches).
Note: A mirrored layout is advantageous for
servicing the drive module.
Punched section
TS 8612.160
(600 mm)
Side mounting plate
TS 8614.240
1100 mm × 300 mm
Auxiliary voltage
transformer
Switch fuse
RDCU
Punched section
TS 8612.160
Base plate
The drive module is placed 30 mm (1.18 in.) from
the right-hand side panel. Fastening point distances
from the bottom of the back mounting plate are
shown.
EMC filter *
PE
Drive module of frame size R7 with bottom exit and Rittal cooling unit
Contactor
Cutting in the door for the
control panel mounting
platform: 115 × 240
(4.53 × 9.45)
Power supply terminal
block of the cooling
unit
C-rail 600 mm
EMC screen *
* required in first environment
installations only
user's cabling