Drive module of frame size R7 with bottom exit and
Rittal cooling unit
What this chapter contains
This chapter describes the installation of a drive module of frame size R7 with
bottom exit into a 600 mm deep, 800 mm wide and 2000 mm high Rittal TS 8
enclosure. A Rittal cooling unit is installed on the side of the enclosure. The degree
of protection of the installation is IP54.
Required Rittal parts
Rittal model no.
Description
TS 8806.500
Enclosure with mounting plate, width x height x depth: 800 mm x 2000 mm x 600 mm
TS 8106.235
Side panel for 2000 mm x 600 mm
TS 8612.160
Punched section with mounting flange, outer mounting level for 600 mm horizontal
TS 8614.240
Mounting plate 1100 × 300
DK 7092.000
C-rail 390 mm
DK 7097.000
C-rail cable clamp for cable diameters of 18 to 22 mm
DK 7098.000
C-rail cable clamp for cable diameters of 38 to 42 mm
DK 7828.060
C-rail 600 mm
SK 3332.540
Cooling unit
SV 3568.000
Laminated copper bar Flexibar S. Dimensions: 15.5 mm x 4.8 mm, 2000 mm long
For photos and specifications of the parts, refer to www.rittal.com.
ACS800-04M parts
The following ACS800-04M parts are used in the installation:
• drive module of type ACS800-04M-xxxx+B060+E202+H352+J400+J410.
For descriptions of the plus codes, refer to ACS800-04/04M/U4 Cabinet Installation
[3AFE68360323 (English)], chapter The ACS800-04/U4 and ACS800-04M: Type
code.
Additional parts to be provided by the installer
The following parts, in addition to the Rittal and ACS800-04M parts listed above, are
needed in the installation:
• for first environment installations: EMC screen mesh which allows cooling air flow
from the cooling unit to the input cable part of the enclosure. See page 26.
Drive module of frame size R7 with bottom exit and Rittal cooling unit
23
Qty
(pcs)
1
2
2
1
1
4
6
1
1
3
Need help?
Do you have a question about the ACS800 and is the answer not in the manual?
Questions and answers