32
ACS800-04M parts
The following ACS800-04 parts are used in the installation:
• drive module of type ACS800-04M-xxxx+B060+H354+H355+H356+H362+J400
+J410.
For descriptions of the plus codes, refer to ACS800-04/04M/U4 Cabinet Installation
[3AFE68360323 (English)], chapter The ACS800-04/U4 and ACS800-04M: Type
code.
Additional parts to be provided by the installer
The following parts, in addition to the Rittal and ACS800-04M parts listed above, are
needed in the installation:
• air baffle, see 37.
• 800 mm × 600 mm piece of wire mesh with max. 10 mm mesh size for fulfilling
IP20 degree of protection of the cabinet. The mesh is placed on the top of the
cabinet frame under the 50 mm spacers on which the cabinet roof lies. See page
39.
• power cable lead-throughs. An example with rubber grommets and a strain relief
bracket is shown on page
ABB with code 64331116, refer to page 11.
• control cable lead-throughs. An example is shown on page 40.
• PE busbar of dimensions 70 mm × 50 mm ×10 mm, copper
• contactor (optional)
• auxiliary voltage transformer when a contactor is installed
• supply disconnecting device and input cable fuses. See ACS800-04/04M/U4
Hardware Manual [3AFE64671006 (English)], chapters Planning the electrical
installation and Technical data.
• terminal for grounding the control cable shields and self-adhesive strain reliefs to
be mounted next to the RDCU Drive Control Unit
• shroud over the input cable terminal connections and output connections of the
disconnecting device.
Moving, unpacking and assembling the drive module
Follow the instructions given in ACS800-04/04M/U4 Cabinet Installation
[3AFE68360323 (English)].
Drive module of frame size R8
40.
EMC power cable lead-throughs are available from