Chapter 1 Introduction

ET-7018Z I/O Specifications:
Analog Input
Input Channels
Input Type
Resolution
Sampling Rate
Accuracy
-3dB Bandwidth
Zero drift
Span drift
Input Impedance
Common Mode Rejection
Normal Mode Rejection
Open Wire Detection
Individual Channel Configurable
Over Voltage Protection
ESD Protection
EFT Protection
Digital Output
Output Channels
Output Type
Max Load Current
Load Voltage
DB-1820
Wire Strip Length
Wire Range
Power Requirements
Power consumption
ET-7000 AIO User Manual, Apr. 2009, V1.04,
10 (Differential)
+/-15 mV, +/-50 mV, +/-100 mV, +/-500 mV, +/-1 V, +/-2.5 V
+/-20 mA, 0~20 mA, 4~20 mA (Requires Optional External 125
Ohm Resistor)
Thermocouple (J, K, T, E, R, S, B, N, C, L, M, LDIN43710)
16-bit
10 samples/ second total
+/-0.1% or better
15.7 Hz
+/-0.5 μV/°C
+/-25 ppm/°C
> 300K Ohm
150 dB min.
100 dB
Yes
Yes
240 Vrms
4 kV Contact for each terminal, and 8 kV Air for random point
4 kV for Power
6 (Sink)
Isolated Open-Collector
700mA/ channel
5 ~ 50 V
DC
4~5 mm
16~24 AWG
0.09 A/24 V
(non-regulated)
DC
EMH-011-104----------22