ICP DAS USA ET-7000 Series User Manual page 18

Ethernet remote i/o module
Hide thumbs Also See for ET-7000 Series:
Table of Contents

Advertisement

Chapter 1 Introduction

ET-7017 I/O Specifications:
Analog Input
Input Channels
Input Type
Resolution
Sampling Rate
Accuracy
Bandwidth
Zero drift
Span drift
Input Impedance
Common Mode Rejection
Normal Mode Rejection
Over Voltage Protection
ESD Protection
EFT Protection
Digital Output
Output Channels
Output Type
Max Load Current
Load Voltage
Power Requirements
Power Consumption
ET-7000 AIO User Manual, Apr. 2009, V1.04,
8 Differential
+/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V
+/-20 mA, 0~20 mA, 4~20 mA (jumper selectable)
16-bit (Normal Mode) / 12-bit (Fast Mode)
10 samples/ second total (Normal Mode) /
50 samples/ second total (Fast Mode)
+/-0.1% (Normal Mode) / +/-0.5% (Fast Mode) or better
15.7 Hz (Normal Mode) / 78. 7Hz (Fast Mode)
+/-20 μV/°C
+/-25 ppm/°C
Voltage: 2 MOhm
Current: 125 Ohm
86 dB min.
100 dB
240 Vrms
4 kV Contact for each terminal, and 8 kV Air for random point
4 kV for Power
4 (Sink)
Isolated Open Collector
700 mA/ channel
5 ~ 50 V
DC
0.10 A/24 V
Max.
DC
EMH-011-104----------18