ET-7017-10 I/O Specifications:
Analog Input
Input Channels
Input Type
Resolution
Sampling Rate
Accuracy
Bandwidth
Zero drift
Span drift
Input Impedance
Common Mode Rejection
Normal Mode Rejection
Over Voltage Protection
ESD Protection
EFT Protection
Power Requirements
Power consumption
*Note1: Single-Ended Mode is not available to current inputs.
ET-7000 AIO User Manual, Apr. 2009, V1.04,
10 differential or 20 single-ended (Note1), software selectable
+/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V
+/-20 mA, 0~20 mA, 4~20 mA (jumper selectable)
16-bit (Normal Mode) / 12-bit (Fast Mode)
10 samples/ second total (Normal Mode) /
50 samples/ second total (Fast Mode)
+/-0.1% (Normal Mode) / +/-0.5% (Fast Mode) or better
15.7 Hz (Normal Mode) / 78.7 Hz (Fast Mode)
+/-20 μV/°C
+/-25 ppm/°C
Voltage: 2 MOhm (Differential), 1 MOhm (Single-ended)
Current: 125 Ohm
86 dB min.
100 dB
Differential: 240 Vrms, Single-ended: 150Vrms
4 kV Contact for each terminal, and 8 kV Air for random point
4 kV for Power
0.11 A/24 V
Max. (non-regulated)
DC
EMH-011-104----------20