Appendix D: Modbus Application Notes

High/Low Alarm of the average value of all AI channels
The average value of all AI channels also can equip with the alarm function like the AI
High/Low Alarm. For the detailed description, please refer the
Register
High alarm for the average value of all AI registers
0=normal
10336
1=alarm
Low alarm for the average value of all AI registers
10337
0=normal
1=alarm
High alarm value for Average value of all AI channels
40198
0 ~ 65535 or –32768 ~ +32767
Low alarm value for Average value of all AI channels
40199
0 ~ 65535 or –32768 ~ +32767
ET-7000 AIO User Manual, Apr. 2009, V1.04, EMH-011-104
AI High/Low
Description
----------
Alarm.
145