UPS2000-G- (6 kVA-20 kVA)
User Manual
Issue 18 (2021-07-16)
Table 4-35 Shallow Discharge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item
Description
Timed
Indicates whether to enable the scheduled
shallow
shallow discharge test. If this parameter is set
discharge
to Enable, the system automatically performs
test
a shallow discharge test when the test
interval arrives and the system meets the
shallow discharge conditions. The parameter
is configurable in any mode.
Time
Set the time interval for shallow discharge
interval
tests. The parameter is configurable in any
mode.
Discharge
Set the proportion of the discharge capacity
ratio
to the total discharge capacity. The
parameter is configurable in any mode.
Figure 4-43 Shallow Discharge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Table 4-36 Shallow Discharge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item
Description
Test
Determine whether to periodically send
notificati
shallow discharge test notifications. The
on
values include Disabled and Enabled. The
default value is Disabled. If the value is
Enabled, the system sends shallow discharge
test notifications. The parameter is
configurable in any mode.
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
Def
Value
aul
Range
t
Val
ue
Dis
Disabled
abl
,
ed
Enabled
60
30–90
day
days
s
20
10%–
%
50%
Def
Value
aul
Range
t
Val
ue
Dis
Disabled
abl
,
ed
Enabled
81