UPS2000-G- (6 kVA-20 kVA)
User Manual
Alarm
Alarm
ID-
Name
Cause
ID
0131-01
Ambien
t
overtem
peratur
e
0133-01
Ambien
t
underte
mperat
ure
Issue 18 (2021-07-16)
Alarm
Alarm
Severit
Clearan
y
ce
Mode
Minor
Automa
tic
Minor
Copyright © Huawei Technologies Co., Ltd.
Impact on the System
An alarm is generated.
D Alarm Handling
Handling Suggestion
Possible causes:
● The ambient
temperature in the
UPS equipment room
exceeds the alarm
threshold (default
value: 40°C).
● The temperature and
humidity transducer
is faulty.
Measures:
● Check the ambient
temperature in the
UPS equipment
room.
● Replace the
temperature and
humidity transducer.
Possible causes:
● The ambient
temperature in the
UPS equipment room
is below the alarm
threshold (default
value: 0ºC).
● The temperature and
humidity transducer
is faulty.
Measures:
● Check the ambient
temperature in the
UPS equipment
room.
● Replace the
temperature and
humidity transducer.
169