UPS2000-G- (6 kVA-20 kVA)
User Manual
Alarm
Alarm
ID-
Name
Cause
ID
0044-03
Incomp
atible
ver.
0044-04
Incomp
atible
ver.
0044-05
Incomp
atible
ver.
0044-06
Incomp
atible
ver.
0045-03
Charger
alarm
Issue 18 (2021-07-16)
Alarm
Alarm
Severit
Clearan
y
ce
Mode
Critical
Manual
/Power-
off
Critical
Manual
/Power-
off
Critical
Manual
/Power-
off
Critical
Manual
/Power-
off
Critical
Manual
/Power-
off
Copyright © Huawei Technologies Co., Ltd.
Impact on the System
The UPS cannot be started.
The UPS cannot be started.
The UPS cannot be started.
The UPS cannot be started.
The charger in the UPS
stops.
D Alarm Handling
Handling Suggestion
Possible cause: Software
and hardware versions
do not match.
Measure: Contact the
manufacturer to load
software.
Possible cause: An error
occurred during
software loading.
Measure: Contact the
manufacturer to load
software.
Possible cause: Software
and hardware versions
do not match.
Measure: Contact the
manufacturer to load
software.
Possible cause: Software
and hardware versions
do not match.
Measure: Contact the
manufacturer to load
software.
Possible cause: The
charger capacitor is
faulty.
Measure: Contact
Huawei technical
support for repair.
159