Step 4 Perform the following operations on each UPS:
Issue 18 (2021-07-16)
NO TE
● The preceding operations are performed when the mains input and bypass input use
different power sources. When they use the same power source, you need only to switch
on the UPS AC input circuit breaker and general AC input circuit breaker.
● If a PDU is configured, switch on the following circuit breakers: general mains input
circuit breaker, general bypass input circuit breaker, mains input circuit breakers for all
UPSs on the PDU, bypass input circuit breakers, and output circuit breakers for all UPSs
on the PDU. The initiation screen is displayed.
Initial startup
When initialization is complete, the setting wizard screen is displayed. You can
set the language (the default language is English), system parameters, and
battery parameters. After you complete the settings, press
screen is displayed.
Non-initial startup
When the initialization is complete, the standby screen is displayed. On the
standby screen, press
Settings > System Parameters > Output to view output settings: if the
system uses three-phase input three-phase output, Output mode is set to
Three-phase; if the system uses three-phase input single-phase output or
single-phase input single-phase output, Output mode is set to Single-phase.
Voltage level and Frequency level are set based on the rated voltage and
frequency. Press ESC to return to the standby screen.