Huawei UPS2000-G-6KRTS User Manual page 123

Hide thumbs Also See for UPS2000-G-6KRTS:
Table of Contents

Advertisement

UPS2000-G- (6 kVA-20 kVA)
User Manual
Item
Input voltage
Input power
factor (100%
resistive load)
No-load loss
Double-power
input
Startup voltage
Diesel generator
input capacity
Table 9-5 15 kVA/20 kVA mains input electrical specifications
Item
Input power
cable
Rated input
voltage
Issue 18 (2021-07-16)
6 kVA
80–280 V AC (When the
voltage is 80–176 V AC, the
load power is linearly
derated to 40%–100%.)
> 0.99
< 54 W
Disabled
120–280 V AC
Minimum 1.5 times the UPS rated capacity
15 kVA
● Single-phase (L/N) input +
PE cable
● Three-phase (L1/L2/L3/N)
input + PE cable
● 208 V AC, 220 V AC, 230 V
AC, or 240 V AC (single-
phase input)
● 380 V AC, 400 V AC, or
415 V AC (three-phase
input)
Copyright © Huawei Technologies Co., Ltd.
9 Technical Specifications
10 kVA
● 80–280 V AC, single-phase
(When the voltage is 80–
176 V AC, the load power
is linearly derated to 40%–
100%.)
● 138–485 V AC, three-phase
(When the voltage is 138–
305 V AC, the load power
is linearly derated to 40%–
100%.)
● > 0.99 (single-phase input)
● > 0.95 (three-phase input)
< 90 W
Disabled
20 kVA
● Single-phase (L/N) input
+ PE cable
● Three-phase (L1/L2/L3/N)
input + PE cable
● 208 V AC, 220 V AC, 230
V AC, or 240 V AC (single-
phase input)
● 380 V AC, 400 V AC, or
415 V AC (three-phase
input)
115