Huawei UPS2000-G-6KRTS User Manual page 168

Hide thumbs Also See for UPS2000-G-6KRTS:
Table of Contents

Advertisement

UPS2000-G- (6 kVA-20 kVA)
User Manual
Alarm
Alarm
ID-
Name
Cause
ID
0045-04
Charger
alarm
0045-06
Charger
alarm
0045-07
Charger
alarm
0045-08
Charger
alarm
0045-09
Charger
alarm
0045-10
Charger
alarm
Issue 18 (2021-07-16)
Alarm
Alarm
Severit
Clearan
y
ce
Mode
Critical
Manual
/Power-
off
Critical
Manual
/Power-
off
Critical
Manual
/Power-
off
Critical
Manual
/Power-
off/
Automa
tic
Critical
Manual
/Power-
off
Critical
Copyright © Huawei Technologies Co., Ltd.
Impact on the System
The charger in the UPS
stops.
The charger in the UPS
stops.
The charger in the UPS
stops. (The 20 kVA has no
action.)
The charger in the UPS
stops.
D Alarm Handling
Handling Suggestion
Possible cause:
● The charger output is
short-circuited.
● The UPS battery
capacity is low.
Measure:
● Rectify battery port
short circuits. After
you clear the alarm,
restart the UPS. If
the alarm persists,
contact Huawei
technical support for
repair.
● Replace the UPS
battery string.
Possible cause: The
charger is faulty.
Measure: Contact
Huawei technical
support for repair.
Possible cause: The
charger is faulty.
Measure: Contact
Huawei technical
support for repair.
160

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents